Categories | Digital Earth Resistance Tester |
---|---|
Place of Origin: | Guangdong, China (Mainland) |
Model Number: | YH302 |
Certification: | CE |
MOQ: | 1 pcs |
Price: | the best price |
Packaging Details: | carton box for outer ,gift box for unit |
Delivery Time: | According to customers' need. |
Payment Terms: | T/T; Western Union; MoneyGram,Paypal |
Supply Ability: | 120000 pcs per/month |
Brand Name: | yh |
Company Info. |
Shenzhen Yehai Sci. & Tech. Deve. Co., Ltd. |
Verified Supplier |
View Contact Details |
Product List |
3 / 4 Pole Digital Earth Resistance Tester Clamp YH302 , Earth Resistance
Quick Detail:
Features
☉ Current Clamp selection method is used to measuring earth resistance without breaking grounding connection
☉ Double clamp without auxiliary electrode is used to fast measuring grounding resistance
☉ Auto and manual control the test frequency have 94Hz, 105Hz, 111Hz, 128Hz four frequency Provide choice. Automatic frequencycontrol (AFC) is automatically identified
interference frequency and then selected the proper measurement frequency , so that reduced the affect of
interference voltage.
☉ Automatically measuring the interference voltage and the leakage current. The limited value will be alarmed.
☉ Auto power off
☉ Clock display
☉ Double battery power supply and low battery indication
☉ Data storage:Can memorize up to 100 measuring values, and uploading to PC by USB2.0 interface.
WARRANTY: one year
Description:
Advanced earth Resistance Tester YH302
The YH302 is advanced intelligent Earth Resistance Tester, which is used to measure grounding resistance for grounding pole connected to some conductive part of facility in the power
distribution unit of power circuit or building structure, for working grounding (the power distribution unit of power circuit is setting some earth electrode for good operating condition),
for safeguard grounding( if the insulation is damaged, the metal case of electric facility and the construct
rack of the power distribution unit or electric pole tower may be electrified.
Therefor, setting safeguard grounding to prevent person and facility from electric damage), for safeguard grounding for the thunder and lightning
(It is seted for thunderstruck safeguard facility is discharg),for static electricity safeguard grounding (to prevent
the inflammable oil, natural gas tin and pipe from static electricity danger).
For grounding pole (It is metal conductor that is buried in the soil and directly in touched with earth), for grounding wire(It is used to connect the ground terminal of electric facility to grounding pole), and for the Grounding Net (It is Large-Size horizontal net grounding unit that is consist of vertial grounding
pole and horizontal grounding pole used forPower House,Transformer Station.
The grounding unit has discharge function and Stabilize voltage ) The tester used for the furnish power, transformer station , it's rated AC voltage up to 500KV.
Specifications
Test mode | voltage | frequency: | resistance |
3 pole & 4 pole | AC 20V/48V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω ~ 300kΩ ±(5%rdg+5dgt) |
3 pole & 4 pole with Current Clamp | AC 20V/48V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω~19.99kΩ ±(5%rdg+5dgt) |
Double Clamp | AC48V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω~150Ω ±(10%rdg+5dgt) |
2 pole R~ | AC20V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω ~ 300kΩ ±(5%rdg+5dgt) |
2 pole /4pole R | DC20V | 0.02Ω ~ 3kΩ ±(5%rdg +5dgt) | |
RK (compensation measurement forwire resistance) | AC20V/48V DC/20V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω~29.99Ω ±(5%rdg+5dgt) |
Test Short Current | ≤ 250 mA | ||
Soil resistivity | AC20V/48V | 94Hz;105Hz;111Hz;128Hz;AFC | 0.02Ω·m~1000kΩ·m ±(5%rdg+5dgt) |
Disturb Voltage; Current and Frequency | Voltage ±1V~±50VDC/AC±(5%rdg+5dgt) Frequency 16Hz~400Hz ±1%rdg+2dgt Current: 20mA~2A;±(5%rdg+5dgt) | ||
USB2.0 interface | |||
Data Storage | Manually store 100 groups | ||
Power Supply | LR14×6; Voltage:9V Recharge Battery:Ni~MH recharge Battery, 7.2V Charger: Input voltage:100V~240V Frequency:50Hz~60Hz Output Voltage:12VDC3A | ||
Display | LCD display, with Back light. Max 9999 | ||
Dimension | 230(W)×125(H)×284(L)mm | ||
Weight | Approx. 2.5kg |